SENSING BULB LOCATION

Q: What is the correct position for the TXV Sensing bulb?

A. The placement of the remote sensing bulb of the TXV onto the suction line is critical to proper TXV performance. The important points to follow are:

• Clean the suction line near the outlet of the evaporator;

• The entire length of the sensing bulb must be in contact with the cleaned portion of the suction line.

• The sensing bulb should be placed several inches downstream of the external equalizer connection.

• The sensing bulb should be attached at 12 o'clock on any suction line of 7/8" diameter or smaller. On lines larger than 7/8" diameter the bulb should be placed at either 4 or 8 o'clock. The bulb should never be placed at 6 o'clock.

• Always insulate the sensing bulb after installation.

• A sensing bulb can be installed on a vertical suction line if necessary but never place bulb downstream of a trap. Bulb placement before a trap (upstream) is recommended.

Emerson Climate Technologies and the Emerson Climate Technologies logo are trademarks and service marks of Emerson Electric Company. Copeland is a registered trademark of Emerson Electric. All other trademarks are property of their respective owners. © 2005 Copeland Corporation.

Emerson Logo

Tools Tools of the Trade with Bob Carrê.
read more >
Jims Tips Jim's Tips.
read more >
Dealer Spotlight Dealer Spotlight – Speer Air.
read more >
Emerson Files The Emerson Files.
Business Card Leave Your Business Card – On Their Wall!
read more >
Payne Cool Customers? Warm Them Up to Payne® Equipment.
read more >
Mobile Office Get a FREE Front Seat Mobile Office!
view offer >
Win Win 2011 Check out the 2011 Win/Win Offers!
view all offers >
   
   

archive